Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability. This vulnerability allows network-adjacent attackers to bypass authentication on affected installations of Socomec DIRIS A-40 power monitoring devices. Authentication is not required to exploit this vulnerability.
The specific flaw exists within the web API implementation, which listens on TCP port 80 by default. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-23993.
CVSS Details
- CVSS 3.0 Base Score: 6.3
- CVSS 3.0 Vector: (CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L)
Prioritise with Active Threat Intelligence
With curated Threat Intelligence, you can see which vulnerabilities truly put you at risk, prioritize what matters most, and act before attackers do.
Explore Intelligence Hub